| Technical data | EL4034 |
|---|---|
| Number of outputs | 4 |
| Power supply | 24 V DC via power contacts |
| Signal voltage | -10…+10 V |
| Distributed clocks | yes |
| Distributed clock precision | << 1 µs |
| Load | > 5 kΩ (short-circuit proof) |
| Resolution | 12 bit |
| Output error | < 0.1% (relative to end value) |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Conversion time | ~ 250 µs |
| Current consumption power contacts | typ. 40 mA |
| Current consumption E-bus | typ. 140 mA |
| Bit width in the process image | 4 x 16 bit AO output |
| Special features | Optional watchdog: user-specific output value with ramp; user synchronization can be activated. |
| Weight | approx. 85 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring level | for all ESxxxx terminals |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, DNV |
| Ex marking |
ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |