input |
type of the power supply network |
1-phase AC or DC |
supply voltage at AC |
|
● minimum rated value |
100 V |
● maximum rated value |
240 V |
● initial value |
85 V |
● full-scale value |
264 V |
input voltage at DC |
110 ... 300 V |
wide range input |
Yes |
overvoltage overload capability |
300 V AC for 1 s |
buffering time for rated value of the output current in the event of power failure minimum |
40 ms |
operating condition of the mains buffering |
at Vin = 187 V |
line frequency |
50/60 Hz |
line frequency |
47 ... 63 Hz |
input current |
|
● at rated input voltage 120 V |
0.3 A |
● at rated input voltage 230 V |
0.2 A |
current limitation of inrush current at 25 °C maximum |
20 A |
I2t value maximum |
0.8 A²·s |
fuse protection type |
internal |
fuse protection type in the feeder |
Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic C |
output |
voltage curve at output |
Controlled, isolated DC voltage |
output voltage at DC rated value |
24 V |
output voltage |
|
● at output 1 at DC rated value |
24 V |
|
|
output voltage adjustable |
No |
relative overall tolerance of the voltage |
3 % |
relative control precision of the output voltage |
|
● on slow fluctuation of input voltage |
0.1 % |
● on slow fluctuation of ohm loading |
0.1 % |
residual ripple |
|
● maximum |
200 mV |
● typical |
30 mV |
voltage peak |
|
● maximum |
300 mV |
● typical |
50 mV |
display version for normal operation |
Green LED for output voltage OK |
behavior of the output voltage when switching on |
No overshoot of Vout (soft start) |
response delay maximum |
0.5 s |
voltage increase time of the output voltage |
|
● typical |
100 ms |
output current |
|
● rated value |
0.6 A |
● rated range |
0 ... 0.6 A; +55 ... +70 °C: Derating 2%/K |
|
|
supplied active power typical |
14.4 W |
bridging of equipment |
No |
efficiency |
efficiency in percent |
81 % |
power loss [W] |
|
● at rated output voltage for rated value of the output current typical |
3.4 W |
● during no-load operation maximum |
0.3 W |
closed-loop control |
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.2 % |
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
2 % |
setting time |
|
● load step 10 to 90% typical |
1 ms |
● load step 90 to 10% typical |
1 ms |
protection and monitoring |
design of the overvoltage protection |
Yes, according to EN 60950-1 |
property of the output short-circuit proof |
Yes |
design of short-circuit protection |
Constant current characteristic |
● typical |
0.8 A |
overcurrent overload capability |
|
● when switching on |
150% Iout rated typ. 200 ms |
● in normal operation |
overload capability 150% Iout rated typ. 200 ms |
enduring short circuit current RMS value |
|
● maximum |
0.8 A |
measuring point for output current |
No |
safety |
galvanic isolation between input and output |
Yes |
galvanic isolation |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
operating resource protection class |
Class II (without protective conductor) |
protection class IP |
IP20 |
EMC |
standard |
|
● for emitted interference |
EN 55022 Class B |
● for mains harmonics limitation |
not applicable |
● for interference immunity |
EN 61000-6-2 |
standards, specifications, approvals |
certificate of suitability |
|
● CE marking |
Yes |
● UL approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
● CSA approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
● EAC approval |
Yes |
● NEC Class 2 |
Yes; according to UL1310, File E151273 |
● SEMI F47 |
Yes |
type of certification |
|
● CB-certificate |
Yes |
MTBF at 40 °C |
4 415 040 h |
standards, specifications, approvals hazardous environments |
certificate of suitability |
|
● IECEx |
No |
● ATEX |
No |
● ULhazloc approval |
No |
● cCSAus, Class 1, Division 2 |
No |
● FM registration |
No |
standards, specifications, approvals marine classification |
shipbuilding approval |
Yes |
Marine classification association |
|
● American Bureau of Shipping Europe Ltd. (ABS) |
Yes |
● French marine classification society (BV) |
Yes |
● Det Norske Veritas (DNV) |
Yes |
● Lloyds Register of Shipping (LRS) |
Yes |
standards, specifications, approvals Environmental Product Declaration |
Environmental Product Declaration |
Yes |
global warming potential [CO2 eq] |
|
● total |
94.5 kg |
● during manufacturing |
1.3 kg |
● during operation |
93.1 kg |
● after end of life |
0.05 kg |
ambient conditions |
ambient temperature |
|
● during operation |
-25 ... +70 °C; with natural convection |
● during transport |
-40 ... +85 °C |
● during storage |
-40 ... +85 °C |
environmental category according to IEC 60721 |
Climate class 3K3, 5 ... 95% no condensation |
connection method |
type of electrical connection |
screw terminal |
● at input |
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
● at output |
+, -: 1 screw terminal each for 0.5 ... 2.5 mm² |
● for auxiliary contacts |
- |
mechanical data |
width × height × depth of the enclosure |
18 × 90 × 53 mm |
installation width × mounting height |
18 mm × 130 mm |
required spacing |
|
● top |
20 mm |
● bottom |
20 mm |
● left |
0 mm |
● right |
0 mm |
fastening method |
Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions |
● DIN-rail mounting |
Yes |
● S7 rail mounting |
No |
● wall mounting |
Yes |
housing can be lined up |
Yes |
net weight |
0.07 kg |