| General information | ||
| Product type designation | DQ 16x24VDC/0.5A ST | |
| Firmware version | ||
| ● FW update possible | No | |
| based on | 6ES7132-6BH01-0BA0 | |
| usable BaseUnits | BU type A0 | |
| Color code for module-specific color identification plate | CC00 | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | |
| ● Isochronous mode | No | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 | |
| Operating mode | ||
| ● DQ | Yes | |
| ● DQ with energy-saving function | No | |
| ● PWM | No | |
| ● Oversampling | No | |
| ● MSO | No | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Input current | ||
| Current consumption, max. | 30 mA; without load | |
| output voltage / header | ||
| Rated value (DC) | 24 V | |
| Power loss | ||
| Power loss, typ. | 1 W | |
| Address area | ||
| Address space per module | ||
| ● Address space per module, max. | 2 byte; + 2 bytes for QI information | |
| Hardware configuration | ||
| Automatic encoding | Yes | |
| ● Mechanical coding element | Yes | |
| ● Type of mechanical coding element | Type A | |
| Selection of BaseUnit for connection variants | ||
| ● 1-wire connection | BU type A0 | |
| ● 2-wire connection | BU type A0 with AUX terminals or potential distributor module | |
| ● 3-wire connection | BU type A0 with AUX terminals or potential distributor module | |
| Digital outputs | ||
| Type of digital output | Source output (PNP, current-sourcing) | |
| Number of digital outputs | 16 | |
| Current-sinking | No | |
| Current-sourcing | Yes | |
| Digital outputs, parameterizable | Yes | |
| output type acc. to IEC 61131, type 0.5 | Yes | |
| Short-circuit protection | Yes; Electronic | |
| ● Response threshold, typ. | 1 A; 0.7 to 1.3 A | |
| Open-circuit detection | Yes | |
| Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) | |
| Controlling a digital input | Yes | |
| Switching capacity of the outputs | ||
| ● with resistive load, max. | 0.5 A | |
| ● with inductive load, max. | 0.5 A | |
| ● on lamp load, max. | 5 W | |
| Load resistance range | ||
| ● lower limit | 48 !& | |
| ● upper limit | 12 k!& | |
| Output current | ||
| ● for signal "1" rated value | 0.5 A | |
| ● for signal "1" permissible range, max. | 0.5 A | |
| ● for signal "0" residual current, max. | 0.1 mA | |
| Output delay with resistive load | ||
| ● "0" to "1", typ. | 50 µs | |
| ● "1" to "0", typ. | 100 µs | |
| Parallel switching of two outputs | ||
| ● for uprating | No | |
| ● for redundant control of a load | Yes | |
| Switching frequency | ||
| ● with resistive load, max. | 100 Hz | |
| ● with inductive load, max. | 0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads" | |
| ● on lamp load, max. | 10 Hz | |
| Total current of the outputs | ||
| ● Current per channel, max. | 0.5 A | |
| ● Current per module, max. | 8 A; see Equipment Manual "Derating curve" | |
| Total current of the outputs (per module) | ||
| horizontal installation | ||
| — up to 40 °C, max. | 8 A | |
| — up to 50 °C, max. | 6 A | |
| — up to 60 °C, max. | 4 A | |
| vertical installation | ||
| — up to 30 °C, max. | 8 A | |
| — up to 40 °C, max. | 6 A | |
| — up to 50 °C, max. | 4 A | |
| Cable length | ||
| ● shielded, max. | 1 000 m | |
| ● unshielded, max. | 600 m | |
| Interrupts/diagnostics/status information | ||
| Diagnostics function | Yes | |
| Substitute values connectable | Yes | |
| Alarms | ||
| ● Diagnostic alarm | Yes | |
| Diagnoses | ||
| ● Monitoring the supply voltage | Yes | |
| ● Wire-break | Yes; Module-wise | |
| ● Short-circuit to M | Yes; Module-wise | |
| ● Short-circuit to L+ | Yes; Module-wise | |
| ● Group error | Yes | |
| Diagnostics indication LED | ||
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
| ● Channel status display | Yes; green LED | |
| ● for channel diagnostics | No | |
| ● for module diagnostics | Yes; green/red DIAG LED | |
| Potential separation | ||
| Potential separation channels | ||
| ● between the channels | No | |
| ● between the channels and backplane bus | Yes | |
| ● Between the channels and load voltage L+ | No | |
| Isolation | ||
| Isolation tested with | 707 V DC (type test) | |
| Standards, approvals, certificates | ||
| Suitable for safety functions | No | |
| Suitable for safety-related tripping of standard modules | No | |
| Ecological footprint | ||
| ● environmental product declaration | Yes | |
| Global warming potential | ||
| — global warming potential, (total) [CO2 eq] | 29.3 kg | |
| — global warming potential, (during production) [CO2 eq] | 3.98 kg | |
| — global warming potential, (during operation) [CO2 eq] | 25.6 kg | |
| — global warming potential, (after end of life cycle) [CO2 eq] | -0.245 kg | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) | |
| ● horizontal installation, max. | 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. total current 1 A | |
| ● vertical installation, min. | -40 °C; = Tmin | |
| ● vertical installation, max. | 50 °C; = Tmax | |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 5 000 m | |
| ● Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) | |
| Relative humidity | ||
| ● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; incl. condensation / frost permitted (no commissioning under condensation conditions) | |
| Resistance | ||
| Coolants and lubricants | ||
| — Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air | |
| Use in stationary industrial systems | ||
| — to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | |
| — to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | |
| — to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * | |
| — Against mechanical environmental conditions acc. to EN 60721-3-3 | Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
| Use on ships/at sea | ||
| — to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request | |
| — to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | |
| — to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * | |
| — Against mechanical environmental conditions acc. to EN 60721-3-6 | Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
| Usage in industrial process technology | ||
| — Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) | |
| — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | |
| Remark | ||
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | |
| Conformal coating | ||
| ● Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability | |
| ● Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection | |
| ● Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life | |
| ● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A | |
| Dimensions | ||
| Width | 15 mm | |
| Height | 73 mm | |
| Depth | 58 mm | |
| Weights | ||
| Weight, approx. | 30 g | |