Measuring Range: User-selectable:
0–10 m/s (0–2000 ft/min)
0–15 m/s (0–3000 ft/min)
0–20 m/s (0–4000 ft/min)
Accuracy: ±(0.2 m/s + 3% of measured value) at 20°C (68°F) and 45% RH
Response Time: Selectable 1 second (fast) or 4 seconds (typical)
Output Signals:
Analog: 0–10 V or 4–20 mA (jumper selectable)
Digital: RS485 with Modbus RTU or BACnet MS/TP
Power Supply: 24 V AC/DC ±20%
Current Consumption:
Analog output: 170 mA @ 24 VAC, 70 mA @ 24 VDC
RS485 output: 120 mA @ 24 VAC, 50 mA @ 24 VDC
Operating Temperature:
Probe: -25°C to 50°C (-13°F to 122°F)
Electronics: -10°C to 50°C (14°F to 122°F)
Enclosure Rating: IP65/NEMA 4 (electronics); IP20 (remote probe)
Mounting: Duct mount with 4 screws; includes mounting flange
Dimensions:
Probe: 8 inches (203 mm)
Enclosure: 90 mm × 110 mm × 46 mm