| Technical data | EL2024 | 
|---|---|
| Connection technology | 2-wire | 
| Number of outputs | 4 | 
| Nominal voltage | 24 V DC (-15%/+20%) | 
| Load type | ohmic, inductive, lamp load | 
| Distributed clocks | – | 
| Max. output current | 2.0 A (short-circuit proof) per channel | 
| Short-circuit current | typ. < 70 A | 
| Reverse voltage protection | yes | 
| Breaking energy | < 1.7 J/channel | 
| Switching times | typ. TON: 40 µs, typ. TOFF: 200 µs | 
| Current consumption E-bus | typ. 120 mA | 
| Current consumption power contacts | typ. 13 mA + load | 
| Bit width in the process image | 4 outputs | 
| Configuration | no address or configuration setting | 
| Electrical isolation | 500 V (E-bus/field potential) | 
| Weight | approx. 55 g | 
| Operating temperature | -25…+60°C | 
| Storage temperature | -40…+85°C | 
| Relative humidity | 95%, no condensation | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. rating/installation pos. | IP20/variable | 
| Pluggable wiring | for all ESxxxx terminals | 
| Approvals/markings | CE, CCC, UL, ATEX, IECEx | 
| Ex marking | 
				ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc  |