| Product Description |
|---|
| Power Feed Module |
| Supply | ||
|---|---|---|
| Connection |
terminals 11+, 12- terminals 8+, 9- |
|
| Rated voltage |
20 ... 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
|
| Fusing |
5 AT/250 V AC recommended maximum utilization of the fuse: 80 % |
|
| Power dissipation | ≤ 1 W | |
| Output | ||
| Connection | Power Rail | |
| Output current | max. 4 A | |
| Output voltage | Ui ≥ rated voltage Ur = Ui - 0.6 V | |
| Fault signal | relay output: NO contact | |
| Contact loading | 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2017 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | UL 22 ATEX 2853 X | |
| Marking |
II 3G Ex ec nC IIC T4 Gc |
|
| Directive conformity | ||
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN IEC 60079-15:2019 | |
| International approvals | ||
| FM approval | FM 22 US 0031 X | |
| Control drawing | 116-0160 | |
| UL approval | E106378 | |
| CSA approval | CoC 1051840 | |
| IECEx approval | ||
| IECEx certificate | IECEx UL 16.0051X | |
| IECEx marking | Ex ec nC IIC T4 Gc | |
| General information | ||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |