| Application Code | 
									EII | 
| Type Version | 
									mk2 | 
| Lamp Type | 
									TL-D | 
| Number of Lamps | 
									1 piece/unit | 
| Number of Products on MCB (16A Type B) (Nom) | 
									28 | 
| Automatic Restart | 
									Yes | 
| Input Voltage | 
									220 to 240 V | 
| Input Frequency | 
									50 to 60 Hz | 
| Operating Frequency (Max) | 
									89 kHz | 
| Operating Frequency (Min) | 
									45 kHz | 
| Ignition Method | 
									Programmed Start | 
| Crestfactor (Max) | 
									1.7 | 
| Power Factor 100% Load (Nom) | 
									0.95 | 
| Ignition Time (Max) | 
									0.2 s | 
| Mains Voltage Performance (AC) | 
									-8%-+6% | 
| Mains Voltage Safety (AC) | 
									-10%-+10% | 
| Earth Leakage Current (Max) | 
									0.5 mA | 
| Inrush Current Width | 
									0.25 ms | 
| Power Losses (Nom) | 
									5.5 W | 
| Inrush Current Peak (Max) | 
									27 A | 
| Connector Type Input Terminals | 
									WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring] | 
| Connector Type Output Terminals | 
									WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring] | 
| Connector Type Control Input Terminals | 
									WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring] | 
| Wire Striplength | 
									8.0-9.0 mm | 
| Dual Fixture Master/Slave | 
									Not applicable  [ Master/Slave oper. not applicable] | 
| Control Input Terminal Cross Section | 
									0.50-1.00 mm² | 
| Input Terminal Cross Section | 
									0.50-1.00 mm² | 
| Output Terminal Cross Section | 
									0.50-1.00 mm² | 
| Auto Insert (ALF/ADS) Wire Cross Section | 
									0.5 mm² | 
| Rated Ballast-Lamp Power | 
									36 W | 
| T-Ambient (Max) | 
									50 °C | 
| T-Ambient (Min) | 
									10 °C | 
| T-Storage (Max) | 
									80 °C | 
| T-Storage (Min) | 
									-25 °C | 
| Stable Lamp Operation Temperature | 
									Not Specified | 
| T-Ignition (Max) | 
									50 °C | 
| T-Ignition (Min) | 
									0 °C | 
| Control Interface | 
									1-10V | 
| Regulating Level Power | 
									1%-100% | 
| Control Input Protection | 
									Yes (Basic insulation) | 
| Housing | 
									L 360x30x21 | 
| Battery Voltage Lamp Ignition | 
									196 V | 
| Battery Voltage Lamp Operation | 
									154-276 | 
| Energy Efficiency Index | 
									A1 BAT | 
| IP Classification | 
									IP 20  [ Ingress Protection 20] | 
| EMI 9 kHz ... 30 MHz | 
									EN55015 | 
| EMI 30 MHz ... 1000 MHz | 
									EN55022 level B | 
| Safety Standard | 
									IEC 61347-2-3 | 
| Performance Standard | 
									IEC 60929 | 
| Quality Standard | 
									ISO 9000:2000 | 
| Environmental Standard | 
									ISO 14001 | 
| Harmonic Current Emission Standard | 
									IEC 61000-3-2 | 
| EMC Immunity Standard | 
									IEC 61547 | 
| Vibration Standard | 
									IEC68-2-6 F c | 
| Bumps Standard | 
									IEC 68-2-29 Eb | 
| Humidity Standard | 
									EN 61347-2-3 clause 11 | 
| Approval Marks | CE marking ENEC certificate VDE-EMV certificate | 
| Temperature Marking | 
									Yes | 
| Emergency Standard | 
									IEC 60598-2-22 | 
| Hum And Noise Level | 
									Inaudible | 
| Full product code | 
									871150091013430 | 
| Order product name | 
									HF-R 136 TL-D EII 220-240V 50/60Hz | 
| EAN/UPC - Product | 
									8711500910134 | 
| Order code | 
									913700609266 | 
| Numerator - Quantity Per Pack | 
									1 | 
| Numerator - Packs per outer box | 
									12 | 
| Material Nr. (12NC) | 
									913700609266 | 
| Net Weight (Piece) | 
									0.260 kg | 
 Malaysia
Malaysia