General information |
Product type designation |
DQ 16x24VDC/0.5A ST |
Firmware version |
|
● FW update possible |
No |
based on |
6ES7132-6BH01-0BA0 |
usable BaseUnits |
BU type A0 |
Color code for module-specific color identification plate |
CC00 |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
● Isochronous mode |
No |
Engineering with |
● STEP 7 TIA Portal configurable/integrated from version |
see entry ID: 109746275 |
Operating mode |
● DQ |
Yes |
● DQ with energy-saving function |
No |
● PWM |
No |
● Oversampling |
No |
● MSO |
No |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
19.2 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption, max. |
30 mA; without load |
output voltage / header |
Rated value (DC) |
24 V |
Power loss |
Power loss, typ. |
1 W |
Address area |
Address space per module |
● Address space per module, max. |
2 byte; + 2 bytes for QI information |
Hardware configuration |
Automatic encoding |
Yes |
● Mechanical coding element |
Yes |
● Type of mechanical coding element |
Type A |
Selection of BaseUnit for connection variants |
● 1-wire connection |
BU type A0 |
● 2-wire connection |
BU type A0 with AUX terminals or potential distributor module |
● 3-wire connection |
BU type A0 with AUX terminals or potential distributor module |
Digital outputs |
Type of digital output |
Source output (PNP, current-sourcing) |
Number of digital outputs |
16 |
Current-sinking |
No |
Current-sourcing |
Yes |
Digital outputs, parameterizable |
Yes |
output type acc. to IEC 61131, type 0.5 |
Yes |
Short-circuit protection |
Yes; Electronic |
● Response threshold, typ. |
1 A; 0.7 to 1.3 A |
Open-circuit detection |
Yes |
Limitation of inductive shutdown voltage to |
Typ. L+ (-50 V) |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● with resistive load, max. |
0.5 A |
● with inductive load, max. |
0.5 A |
● on lamp load, max. |
5 W |
Load resistance range |
● lower limit |
48 !& |
● upper limit |
12 k!& |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range, max. |
0.5 A |
● for signal "0" residual current, max. |
0.1 mA |
Output delay with resistive load |
● "0" to "1", typ. |
50 µs |
● "1" to "0", typ. |
100 µs |
Parallel switching of two outputs |
● for uprating |
No |
● for redundant control of a load |
Yes |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads" |
● on lamp load, max. |
10 Hz |
Total current of the outputs |
● Current per channel, max. |
0.5 A |
● Current per module, max. |
8 A; see Equipment Manual "Derating curve" |
Total current of the outputs (per module) |
horizontal installation |
— up to 40 °C, max. |
8 A |
— up to 50 °C, max. |
6 A |
— up to 60 °C, max. |
4 A |
vertical installation |
— up to 30 °C, max. |
8 A |
— up to 40 °C, max. |
6 A |
— up to 50 °C, max. |
4 A |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Substitute values connectable |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
Diagnoses |
● Monitoring the supply voltage |
Yes |
● Wire-break |
Yes; Module-wise |
● Short-circuit to M |
Yes; Module-wise |
● Short-circuit to L+ |
Yes; Module-wise |
● Group error |
Yes |
Diagnostics indication LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
● Channel status display |
Yes; green LED |
● for channel diagnostics |
No |
● for module diagnostics |
Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
● between the channels |
No |
● between the channels and backplane bus |
Yes |
● Between the channels and load voltage L+ |
No |
Isolation |
Isolation tested with |
707 V DC (type test) |
Standards, approvals, certificates |
Suitable for safety functions |
No |
Suitable for safety-related tripping of standard modules |
No |
Ecological footprint |
● environmental product declaration |
Yes |
Global warming potential |
— global warming potential, (total) [CO2 eq] |
29.3 kg |
— global warming potential, (during production) [CO2 eq] |
3.98 kg |
— global warming potential, (during operation) [CO2 eq] |
25.6 kg |
— global warming potential, (after end of life cycle) [CO2 eq] |
-0.245 kg |
Ambient conditions |
Ambient temperature during operation |
● horizontal installation, min. |
-40 °C; = Tmin (incl. condensation/frost) |
● horizontal installation, max. |
70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. total current 1 A |
● vertical installation, min. |
-40 °C; = Tmin |
● vertical installation, max. |
50 °C; = Tmax |
Altitude during operation relating to sea level |
● Installation altitude above sea level, max. |
5 000 m |
● Ambient air temperature-barometric pressure-altitude |
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Relative humidity |
● With condensation, tested in accordance with IEC 60068-2-38, max. |
100 %; incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance |
Coolants and lubricants |
— Resistant to commercially available coolants and lubricants |
Yes; Incl. diesel and oil droplets in the air |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 |
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3S4 incl. sand, dust, * |
— Against mechanical environmental conditions acc. to EN 60721-3-3 |
Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) |
Use on ships/at sea |
— to biologically active substances according to EN 60721-3-6 |
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 |
Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 |
Yes; Class 6S3 incl. sand, dust; * |
— Against mechanical environmental conditions acc. to EN 60721-3-6 |
Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) |
Usage in industrial process technology |
— Against chemically active substances acc. to EN 60654-4 |
Yes; Class 3 (excluding trichlorethylene) |
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 |
Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 |
* The supplied plug covers must remain in place over the unused interfaces during operation! |
Conformal coating |
● Coatings for printed circuit board assemblies acc. to EN 61086 |
Yes; Class 2 for high reliability |
● Protection against fouling acc. to EN 60664-3 |
Yes; Type 1 protection |
● Military testing according to MIL-I-46058C, Amendment 7 |
Yes; Discoloration of coating possible during service life |
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A |
Yes; Conformal coating, Class A |
Dimensions |
Width |
15 mm |
Height |
73 mm |
Depth |
58 mm |
Weights |
Weight, approx. |
30 g |