6AG1132-6BH01-7BA0 SIPLUS ET 200SP DQ 16x24VDC/0,5A ST

6AG1132-6BH01-7BA0 SIPLUS ET 200SP DQ 16x24VDC/0,5A ST

Kategori: SIEMENS Simatic Control Systems Tersedia
Untuk informasi lebih lanjut, kunjungi situs resmi kami di geasb.com

Deskripsi

General information
Product type designation DQ 16x24VDC/0.5A ST
Firmware version  
● FW update possible No
based on 6ES7132-6BH01-0BA0
usable BaseUnits BU type A0
Color code for module-specific color identification plate CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version see entry ID: 109746275
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Oversampling No
● MSO No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 30 mA; without load
output voltage / header
Rated value (DC) 24 V
Power loss
Power loss, typ. 1 W
Address area
Address space per module
● Address space per module, max. 2 byte; + 2 bytes for QI information
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0
● 2-wire connection BU type A0 with AUX terminals or potential distributor module
● 3-wire connection BU type A0 with AUX terminals or potential distributor module
Digital outputs
Type of digital output Source output (PNP, current-sourcing)
Number of digital outputs 16
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
output type acc. to IEC 61131, type 0.5 Yes
Short-circuit protection Yes; Electronic
● Response threshold, typ. 1 A; 0.7 to 1.3 A
Open-circuit detection Yes
Limitation of inductive shutdown voltage to Typ. L+ (-50 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● with inductive load, max. 0.5 A
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 !&
● upper limit 12 k!&
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, max. 0.5 A
● for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
● "0" to "1", typ. 50 µs
● "1" to "0", typ. 100 µs
Parallel switching of two outputs
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads"
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A
● Current per module, max. 8 A; see Equipment Manual "Derating curve"
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max. 8 A
— up to 50 °C, max. 6 A
— up to 60 °C, max. 4 A
vertical installation
— up to 30 °C, max. 8 A
— up to 40 °C, max. 6 A
— up to 50 °C, max. 4 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes; Module-wise
● Short-circuit to M Yes; Module-wise
● Short-circuit to L+ Yes; Module-wise
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ No
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
Suitable for safety-related tripping of standard modules No
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 29.3 kg
— global warming potential, (during production) [CO2 eq] 3.98 kg
— global warming potential, (during operation) [CO2 eq] 25.6 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.245 kg
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -40 °C; = Tmin (incl. condensation/frost)
● horizontal installation, max. 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. total current 1 A
● vertical installation, min. -40 °C; = Tmin
● vertical installation, max. 50 °C; = Tmax
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max. 100 %; incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
Coolants and lubricants
— Resistant to commercially available coolants and lubricants Yes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3 Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3 Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3 Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6 Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6 Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6 Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6 Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4 Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 * The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
● Coatings for printed circuit board assemblies acc. to EN 61086 Yes; Class 2 for high reliability
● Protection against fouling acc. to EN 60664-3 Yes; Type 1 protection
● Military testing according to MIL-I-46058C, Amendment 7 Yes; Discoloration of coating possible during service life
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A Yes; Conformal coating, Class A
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 30 g

Lihat detail lebih lanjut tentang Green Energy Automation Sdn Bhd
Green Energy Automation Sdn Bhd
Green Energy Automation Sdn Bhd Industrial Process Automation & Control Systems Johor, PLC System Integration Services Malaysia | Green Energy Automation Sdn Bhd