Specifications
            
                
                - Protection rating: 
IP20
- Input: 
1 x sensor input two-wire 8/16 mA
- Output: 
-1 x operating relay (SPDT)
-Optionally 1 x fail safe relay output (SPDT)
- Ambient temperature: 
-20 ... 60 °C
- Signal input (specify): 
Two-wire 8/16 mA
- Signal output (specify): 
-Operating relay
-Fail safe relay
- Approvals: 
-ATEX / Europe
-CSA / Canada
-FM / USA
-IEC / worldwide
- Explosion Protection: 
-Intrinsic safety "i"
-Dust explosion protection through housing "t"
- Overfill protection: 
WHG
- SIL qualification: 
SIL2
- Display & adjustment: 
DIP switch
- Indication: 
LED
 
        
        详情
        Single channel controller for level detection
Transmission of 8/16 mA signals for level signalling (single channel)
Application area
The VEGATOR 121 is a signal conditioning instrument for level detection for the vibrating level switches VEGASWING, VEGAVIB and VEGAWAVE with electronics version ''Two-wire 8/16 mA“. With this instrument simple control Tasks can be solved. Typical applications are monitoring functions such as overflow or dry run protection. Optionally a false signal output is available.
Advantages
	- Comprehensive monitoring detects short-circuit and line break of the measuring cable and interferences in the sensor
- Simple and comfortable SIL and WHG function test by means of test key
- Simple installation through carrier rail mounting as well as detachable, coded terminals
Technical data
	
		
			| Input | 1 x sensor input two-wire 8/16 mA | 
		
			| Output | 1 x relay output (SPDT) optionally
 1 x fail safe relay output (SPDT)
 | 
		
			| Operating voltage | 20 … 253 V AC, 50/60 Hz | 
		
			| Mounting | carrier rail 35 x 7.5 acc. to EN 50022 | 
		
			| SIL qualification | optionally up to SIL2 | 
	
Refer to the link for more details: https://www.vega.com/en/home_de/products/product-catalog/signal-conditioning/controllers/vegator-121