| Power supply circuit | ||
| Through an external power supply unit | 100...240 V ac / 12 V dc | |
| Frequency | 50...60 Hz | |
| Consumption | 15 V·A | |
| Operating temperature | 0...+40 ºC | |
| Altitude | ≤ 2 000 m | |
| Humidity of operation | 80 % for temperatures under 31 ºC, with a linear decrease down to 50 % at 40 ºC | |
| Metering circuit | Three-phase (3 wires) | Three-phase (3 / 4 wires) |
| Voltage circuit | ||
| Measurement range | In accordance with the clamp, 0.01 A...20 kA | |
| Voltage and current transformation ratios | Programmable | |
| Measurement units | Automatic change of scale | |
| Internal memory | 1 Mb | |
| Accuracy class (*) | ||
| Voltage | 0.5 % ± 2 digits | |
| Current | 0.5 % ± 2 digits | |
| Active power | 1 % ± 2 digits | |
| Power factor | 1 % ± 2 digits | |
| Build features(*) | ||
| Housing | Reinforced insulation | |
| Keyboard / Display | On the front panel | |
| Display | LCD 160 x 160 pixels (backlit) | |
| Current clamp connector | 3 | 3 / 4 |
| Dimensions | 220 x 60 x 130 mm | |
| Weight | 800 g | |
| RS-232 Outputs | Series output | |
| Safety | Category III - 600 V, in accordance with 61010 | |
| Standards | ||
| EN 61000-3-2 (1995), Harmonics | ||
| EN 61000-3-3 (1995), Voltage fluctuations | ||
| EN 61000-6-4 (2002), Industrial emissions EN 55011 (1994), Driven (EN 52022 – Class B) EN 55011 (1994), Radiated (EN 55022 – Class A) |
||
| EN 61000-6-2 (2022), Industrial immunity EN 61000-4-2 (1995), Electrostatic discharge ENV 50140 (1993), Radiated electromagnetic field EN 61000-4-8 (1995), Rapid transient bursts ENV 50141 (1993), RF in common mode EN 61000-4-8 (1995), Magnetic field at 50 Hz |
||
| EN 61000-6-1 (2002), Domestic immunity EN 61000-4-5 (1995), Shockwave EN 61000-4-11 (1994), Power supply interruptions |
||
| (*) Accuracy is given by the following measurement conditions: Exclusion of errors produced by the clamps and external voltage transformers, with a range of temperature of 5 ... 45 ºC and power factor of 0 ... 1 |