| Models | 30K | 40K | 50K | 60K |
| Input DC (PV side) | ||||
| Recommended max. PV array size | 60 kW | 80 kW | 100 kW | 100 kW |
| Max. usable PV input power | 60 kW | 80 kW | 100 kW | 100 kW |
| Max. input voltage | 1000 V | |||
| Rated voltage | 600 V | |||
| Start-up voltage | 180 V | |||
| MPPT voltage range | 150 - 850 V | |||
| Max. input current | 3 × 42 A | 4 × 42 A | ||
| Max. current per DC input | 42 A | |||
| Max. short circuit current | 3 × 60 A | 4 × 60 A | ||
| MPPT number / Max. input strings number | 3 / 6 | 4 / 8 | ||
| Battery | ||||
| Battery type | Li-ion | |||
| Battery voltage range | 150 - 800 V | |||
| Max. charge / discharge current | 80 A × 2 | 84 A × 2 | ||
| Number of battery ports | 2 | |||
| Max. charge / discharge power of each input | 33 kW | 35 kW | ||
| Communication | CAN / RS485 | |||
| Output AC (Back-up) | ||||
| Rated output power | 30 kW | 40 kW | 50 kW | 60kW |
| Max. apparent output power | 1.6 times of rated power, 2 s; 1.5 times of rated power, 10 s | |||
| Back-up switch time | < 10 ms | |||
| Rated output voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | |||
| Rated frequency | 50 Hz / 60 Hz | |||
| THDv (@linear load) | < 2% | |||
| Input AC (Grid side) | ||||
| Max. input current | 91.2 A / 86.6 A | 121.6 A / 115.4 A | 152 A / 144.4 A | 152 A / 152 A |
| Input AC (Generator) | ||||
| Max. input power | 30 kW | 40 kW | 50 kW | 60 kW |
| Rated input current | 45.6 A / 43.3 A | 60.8 A / 57.7 A | 76 A / 72.2 A | 91.2 A / 86.6 A |
| Rated input voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | |||
| Rated input frequency | 50 Hz / 60 Hz | |||
| Output AC (Grid side) | ||||
| Rated output power | 30 kW | 40 kW | 50 kW | 60 kW |
| Max. apparent output power | 30 kVA | 40 kVA | 50 kVA | 60 kVA |
| Rated grid voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | |||
| Rated grid frequency | 50 Hz / 60 Hz | |||
| Rated grid output current | 45.6 A / 43.3 A | 60.8 A / 57.7 A | 76 A / 72.2 A | 91.2 A / 86.6 A |
| Power factor | > 0.99 (0.8 leading - 0.8 lagging) | |||
| THDi | < 3% | |||
| Efficiency | ||||
| Max. efficiency | 97.7% | |||
| EU efficiency | 97.3% | |||
| Battery charged efficiency | 98.5% | |||
| Battery discharged efficiency | 97.5% | |||
| Protection | ||||
| Surge protection | DC Type II / AC Type II | |||
| Output over current protection | Yes | |||
| Integrated DC switch | Yes | |||
| DC reverse-polarity protection | Yes | |||
| Protection class / Over voltage category | I / PV II, battery II, AC III | |||
| Integrated AFCI 2.0 | Optional | |||
| General Data | ||||
| Max. allowable phase imbalance (grid & back-up) | 100% | |||
| Max. power per phase (grid & back-up) | 33% | |||
| Dimensions (W × H × D) | 530 × 880 × 290 mm | |||
| Weight | 76 kg | |||
| Topology | Transformerless | |||
| Operating ambient temperature range | -25 ~ +60°C | |||
| Relative humidity | 0 - 100% | |||
| Ingress protection | IP66 | |||
| Cooling concept | Intelligent fan-cooling | |||
| Max. operation altitude | 4000 m | |||
| Grid connection standard | G99, VDE-AR-N 4105/VDE V 0124, EN 50549-1/EN 50549-10, PTPiREE, VDE 0126/XP C15/VFR:2019, NTS 631/RD 1699/RD 244/UNE 217002, CEI 0-21, C10/11, NRS 097-2-1, TOR, EIFS 2018.2, IEC 62116, IEC 61727, DEWA, MEA, PEA, PORTARIA Nº 140/PORTARIA Nº 515 |
|||
| Safety / EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4, EN 55011 | |||
| Features | ||||
| PV connection | MC4 connector | |||
| Battery connection | Terminal connector | |||
| AC connection | OT terminal | |||
| Display | 7.0'' LCD display & Bluetooth + APP | |||
| Communication | CAN, RS485-115200, Optional: Wi-Fi, Cellular, LAN | |||