Comet T6340 Specifications |
|
Technical Parameters |
Value |
|
Output |
RS232 |
|
Measured Value |
CO2 + Temperature + Relative Humidity |
|
Construction Type |
Ambient Air |
|
Design |
Industrial |
|
Temperature Measuring Range |
-30 to 60 °C |
|
Relay Output |
No |
|
Two-State Input |
No |
|
Lcd Display |
Yes |
|
PoE |
No |
|
Range of CO2 concentration measurement |
0 to 2000 ppm |
|
Accuracy of CO2 concentration measurement |
±(50ppm +2% from reading) at 25°C and 1013hPa |
|
Optional range of CO2 concentration measurement |
0 to 10000ppm ±(100ppm +5% from reading) at 25°C and 1013hPa |
|
Relative humidity range |
0 to 100% |
|
Accuracy of relative humidity measurement |
±2.5% relative humidity from 5 to 95% at 23°C |
|
Accuracy of temperature output |
±0.4°C |
|
Available temperature units |
degrees Celsius, Fahrenheit |
|
Accuracy and range of dew point temperature output - for more details see graphs |
±1.5°C at ambient temperature T<25°C and RH>30%
range -60 to +80 °C |
|
Accuracy and range of absolute humidity output |
±1.5g/m3 at ambient temperature T < 25°C
range 0 to 400 g/m3 |
|
Accuracy and range of specific humidity output |
±2g/kg at ambient temperature T < 35°C
range 0 to 550 g/kg |
|
Accuracy and range of mixing ratio output |
±2g/kg at ambient temperature T < 35°C
range 0 to 995 g/kg |
|
Accuracy and range of specific enthalpy output |
±3kJ/kg at ambient temperature T < 25°C
range: 0 to 995 kJ/kg |
|
Measuring interval of CO2 |
15s |
|
Temperature operating range |
-30 to +60°C |
|
Communication protocol |
ModBus RTU and Advantech ADAM compatible protocol |
|
Communication speed |
110 to 115200 Bd |
|
Filtering ability of sensor cover |
0.025mm - filter with stainless steel mesh |
|
Protection of the case with electronics |
IP30 electronics, IP40 sensors |
|
Power |
9-30Vdc, power consumption approximately 1W |
|
Dimensions |
88.5 x 170 x 39.5 mm (W x H x D), stem length 75 mm |
|
Weight |
approximately 175g |